Information & News

Three Neutral Earthing Resistors Manufactured in Brisbane by Backer Cynebar Ohmic Featuring Bender Monitoring Technology

by JN ·

Two 11kV 120A Neutral Earthing Resistors in 316 stainless steel enclosures, one closed and one open

Enhancing Network Protection with Proven Australian and European Expertise

Backer Cynebar Ohmic recently completed the manufacture of three custom Neutral Earthing Resistors (NERs) in Brisbane, Australia, designed for installation on 11kV/6.35kV electrical distribution networks. The project combined Backer Cynebar Ohmic's local manufacturing capability with premium monitoring and protection equipment from Bender, a global leader in grounding and insulation monitoring solutions.

The NERs were designed with the following electrical characteristics:

ParameterSpecification
System Voltage11kV / 6.35kV
Rated Current120A
Duty Rating10 Seconds
Resistance Value52.9 Ohms
Ground Fault MonitoringBender System
Open stainless steel Neutral Earthing Resistor enclosure showing stacked resistor elements
Neutral Earthing Resistor, 11kV/6.35kV, 120 Amp, 10 seconds, 52.9 Ohms. Enclosure 316 SS

These units provide controlled limitation of earth fault current while enabling continuous monitoring of the grounding system, improving both personnel safety and network reliability.

Why Neutral Earthing Resistors Are Critical

Neutral Earthing Resistors are installed between the transformer or generator neutral point and earth to limit earth fault currents to a predetermined value.

By limiting fault current to 120A, these NERs provide several important benefits:

  • Reduced thermal and mechanical stress on switchgear and transformers.
  • Minimized equipment damage during line-to-ground faults.
  • Lower arc flash energy levels.
  • Improved system stability during transient fault events.
  • Easier fault location and protection coordination.
  • Reduced repair costs and network downtime.

For medium-voltage networks, resistor earthing remains one of the most widely adopted methods of balancing personnel safety, equipment protection, and system continuity.

Closed stainless steel Neutral Earthing Resistor enclosure with 120A NER nameplate and high voltage danger sign
Neutral Earthing Resistor, IP54 316SS Enclosure

Advanced Ground Fault Monitoring with Bender Technology

For this project, the customer specified Bender protection equipment, recognised worldwide for its high reliability and specialist focus on grounding and insulation monitoring solutions.

Bender CD14400 Sensing Resistor

The Bender CD14400 sensing resistor provides an accurate voltage reference across the NER during earth fault conditions.

Key advantages include:

  • Highly accurate earth fault measurement.
  • Stable performance under varying environmental conditions.
  • Designed specifically for medium-voltage grounding applications.
  • Reliable operation during fault events and transient conditions.
  • Seamless integration with Bender NER monitoring systems.
Bender CD14400 coupling device mounted inside the NER enclosure with red high voltage cable
Coupling for NGR, BENDER CD14400

The sensing resistor allows the monitoring system to accurately assess the condition of the grounding circuit while maintaining long-term reliability in service.

Bender NGRM550 Neutral Grounding Resistor Monitor

The Bender NGRM550 is one of the industry's most advanced Neutral Grounding Resistor monitoring relays.

Unlike traditional protection schemes that only operate during an earth fault, the NGRM550 continuously supervises the health of the grounding resistor circuit.

Yellow Bender NGRM550 monitoring relay wired inside a stainless steel terminal box
Neutral Earthing Resistor with Bender Relay NGRM550

Continuous NER Integrity Monitoring

The relay continuously monitors:

  • Neutral earthing resistor continuity.
  • Open-circuit resistor conditions.
  • Degradation of grounding connections.
  • Wiring faults within the monitoring circuit.

This allows issues to be identified before a genuine network fault occurs.

Improved Network Safety

A failed or disconnected NER can leave a network effectively ungrounded, increasing the risk of:

  • Dangerous overvoltages.
  • Insulation stress.
  • Equipment damage.
  • Difficult-to-locate earth faults.
  • Increased personnel safety risks.

The NGRM550 provides immediate alarm indication should abnormal conditions be detected, allowing corrective action before system reliability is compromised.

Reduced Maintenance Requirements

Continuous online monitoring reduces the need for routine manual inspection and testing while providing early warning of potential problems.

SCADA and Protection System Integration

The NGRM550 can be easily integrated with:

  • SCADA systems.
  • PLC control platforms.
  • Substation monitoring systems.
  • Industrial power management networks.

This provides maintenance and operations personnel with real-time visibility of grounding system health.

Australian Manufactured for Australian Conditions

All three NERs were engineered and manufactured by Backer Cynebar Ohmic in Brisbane using proven resistor technology developed for Australian utility, mining, rail, renewable energy and industrial applications.

Side view of the stainless steel NER enclosure with attached terminal and monitoring boxes in the Brisbane workshop
Neutral Earthing Resistor manufactured in Brisbane

Benefits of local manufacture include:

  • Faster delivery schedules.
  • Local engineering consultation and support.
  • Compliance with Australian standards and customer specifications.
  • Easier future maintenance and spare parts support.
  • Reduced project risk compared with imported alternatives.
  • Direct access to technical expertise throughout the project lifecycle.

The result is a robust grounding solution specifically designed for the demanding operating conditions commonly encountered throughout Australia.

Delivering Reliable Ground Fault Protection

These three 11kV Neutral Earthing Resistors demonstrate how combining locally manufactured resistor technology with world-class Bender monitoring equipment can significantly improve the safety and reliability of medium-voltage electrical networks.

By incorporating the Bender CD14400 sensing resistor and Bender NGRM550 monitoring relay, Backer Cynebar Ohmic has delivered a complete grounding solution that not only limits earth fault current to 120A but continuously verifies the integrity of the grounding system.

For utilities, rail operators, mining companies, renewable energy facilities and industrial plants, this approach provides enhanced network protection, improved visibility of grounding system health, reduced maintenance costs and greater confidence in the long-term performance of critical electrical infrastructure.

Need advice on your application?

Tell us about your application and our engineers will find the right solution.

Talk to an engineer